• Home
  • About Us
  • Rep List
  • Options
  • Contact Us
  • Products
  • Sizing
  • ES-MBA Parts
  • Installation Manuals
  •  
  • HVAC
  • Direct Steam Heating
  • Humidification
  • Vessel Heating
  • Hot Water for Process
    & Comfort Heating
  • Distillation, Sterilization
    & Autoclave Use
  • Clean Steam: Pharmaceuticals,
    Cosmetics & Food Processes
  • Processing Waxes.
    Paraffin & Glues
  • Heat Pump Auxiliary
    Heating
  • Anti-freeze Protection,
    Preheating & Fuel Oil Lines
  • Bakery Overs, Proofers
  • Jacketed Reactors
  • In-line Steam Superheating
  • Microbreweries
  • On-site Power Plant
    & Utility Steam
  • Air, Water, Oil Preheating
    and Booster Heating
  • Environmental Rooms,
    Test Chambers and Ovens
  • Laboratory/Experiment
    Environments
  • Steam for
    Jacketed Kettles
  • Food Manufacturing
     
  • SVW IOM
  • MBA IOM
  • ES/SSB/HU IOM
  • SVS IOM
  • ES24A IOM
  • ES30A/ES36A/HP30A
Print Page

MBA Electric Steam Generator Specifications


1. All units are physically identical and have a packed shipping weight of 125 LBS.
2. Units are trimmed at 100 PSIG as standard . Lower trims are available.
3. Incoming water line pressure must be 10 PSIG greater than generator operating pressure. If not, a motor/pump must be used. Specify Sussman 38002A high pressure feedwater motor/pump system.
4. When ordering: Specify Model No., KW, volts/ph and motor/pump, if required.
5. Water connection is 1/4 NPT. Steam outlet is 1/2 NPT.
DIMENSIONAL INFORMATION
SYMBOL
INCHES
A
20 1/2
B
17 1/2
C
17 7/8
D
15 3/4

MODEL
KW
VOLTS
PH
AMPS
PPH
MBA3
3
120, 208, 240
1
25, 15, 13
9
MBA6
6
208, 240, 480
3
17, 15, 8
18
MBA9
9
208, 240, 480
3
25, 22, 11
27
MBA12
12
208, 240, 480
3
34, 29, 15
36
MBA18
18
208, 240, 480
3
50, 44, 22
54
MBA20
20
208, 240, 480
3
56, 49, 25
60

SYMBOL
DESCRIPTION
1
STRAINER
2
WATER SOLENOID
3
CHECK VALVE
4
DRAIN VALVE
5
STEAM OUTLET
6
GAUGE GLASS ASSEMBLY
7
SAFETY VALVE
8
PRESSURE GAUGE
9
HI-LIMIT PRESSURE CONTROL
10
OPERATING PRESSURE CONTROL
11
ACCESS PANEL
12
ON/OFF SWITCH

<<Return to MBA Main Page >>

 

HOME | ABOUT US | REP LIST | PRODUCTS | SIZING | ES-MBA PARTS | MBA IOM | ES/SSB/HU IOM | TECH SPECS | PRIVACY POLICY | SITEMAP | CONTACT US

Sussman Electric Boilers

A Division of SUSSMAN-AUTOMATIC CORP.

1-800-238-3535

43-20 34th Street • Long Island City, New York 11101

Tel: 718-937-4500 • Fax: 718-937-4676

e-mail: seb@sussmancorp.com
info@sussmancorp.com

© 2008 Sussman Boilers.