DIMENSIONAL
INFORMATION
|
|
SYMBOL
|
INCHES
|
|
A
|
20
1/2
|
|
B
|
17
1/2
|
|
C
|
17
7/8
|
|
D
|
15
3/4
|
|
|
MODEL
|
KW
|
VOLTS
|
PH
|
AMPS
|
PPH
|
|
MBA3
|
3
|
120,
208, 240
|
1
|
25,
15, 13
|
9
|
|
MBA6
|
6
|
208,
240, 480
|
3
|
17,
15, 8
|
18
|
|
MBA9
|
9
|
208,
240, 480
|
3
|
25,
22, 11
|
27
|
|
MBA12
|
12
|
208,
240, 480
|
3
|
34,
29, 15
|
36
|
|
MBA18
|
18
|
208,
240, 480
|
3
|
50,
44, 22
|
54
|
|
MBA20
|
20
|
208,
240, 480
|
3
|
56,
49, 25
|
60
|
|
|
SYMBOL
|
DESCRIPTION
|
|
1
|
STRAINER
|
|
2
|
WATER
SOLENOID
|
|
3
|
CHECK
VALVE
|
|
4
|
DRAIN
VALVE
|
|
5
|
STEAM
OUTLET W/STEAM VALVE
|
|
6
|
GAUGE
GLASS ASSEMBLY
|
|
7
|
SAFETY
VALVE
|
|
8
|
PRESSURE
GAUGE
|
|
9
|
HI-LIMIT
PRESSURE CONTROL
|
|
10
|
OPERATING
PRESSURE CONTROL
|
|
11
|
ACCESS
PANEL
|
|
12
|
ON/OFF
SWITCH
|
|
| 1. |
All
units are physically identical and have a packed
shipping weight of 125 LBS. |
| 2. |
Units
are trimmed at 100 PSIG as standard . Lower trims
are available. |
| 3. |
Incoming
water line pressure must be 10 PSIG greater than
generator operating pressure. If not, a motor/pump
must be used. Specify Sussman 38002A high pressure
feedwater motor/pump system. |
| 4. |
When
ordering: Specify Model No., KW, volts/ph and motor/pump,
if required. |
| 5. |
Water
connection is 1/4 NPT. Steam outlet is 1/2 NPT. |